Title |
Point Beach Nuclear Plant Application Study For Power System Stabilizers |
Abstract |
Dynamic stability problems have been experienced with a generator connected to an infinite bus through a long transmission line. Nuclear turbine-generator units #1 and #2 at the Winsconsin Electric Power Point Baech Station were found to be dynamically unstable when one unit is isolated on one of the lines to Milwaukee or when two units are isolaed on the lines to milwaukee. Power System Stabilizers(PSS) were applied to the excitation system to provide stable operation under these conditions. Suitable settings for the PSS were predetetermined analytically by computer method and root licus analysis of an equivalent single machine-infinite bus configuration. This procedure allows graphical approach to the design of power stabilizers and serves as assynthesis procedure when the design constraints are relaxed so the the speed stabilizer is required ro provide animprovement in system damping. A simplified model of the complete exciter generator system is shown to be adequate for this type of analysis. |