Title |
Environmental effects by corona discharge from a 765kV double circuit transmission line |
Authors |
김정부 ; 이동일 ; 신구용 ; 양광호 ; 안희성 ; 구자윤 |
Keywords |
Corona ; Audible Noise ; Environmental Impact ; ; Test Line |
Abstract |
This paper specified the measurement results conducted by the Korea Electric Power Research Institute (KEPRI) 765kV double circuit transmission test line that measured the audible noise, hum noise, radio interference, electric field and aeolian measurement. This test line consists of 6-480mm^{2} conductors per phase. The analysis of the test results shows that this 6-Rail conductor bundle satisfies the audible noise criterion under the stable rainy weather condition and the radio interference level under the fair weather. And the other items are also agreed with the design level criterion. (author). 9 refs., 7 figs., 2 tabs. |