Title |
Advanced Protective Coordination Schemes of Utility Interconnected Cogeneration Systems |
Authors |
최준호(Choe, Jun-Ho) ; 정성교(Jeong, Seong-Gyo) ; 추동욱(Chu, Dong-Uk) ; 김낙경(Kim, Nak-Gyeong) ; 손학식(Son, Hak-Sik) ; 김재철(Kim, Jae-Cheol) |
Keywords |
Cogeneration ; Protective coordination ; Recloser ; Sectionalizer ; Faults current ; Power distribution systems ; PSCAD/EMTDC |
Abstract |
Recently, there has been growing interest in utilizing cogeneration(COGN) systems with a high-energy efficiency due to the increasing energy consumption and the lacking of energy resource. But an insertion of COGN system to existing power distribution system can cause several problems such as voltage variations, harmonics, protective coordination, increasing fault current etc, because of reverse power of COGN, especially in protective coordination. A study on a proper coordination with existing one is being required. The existing power distribution system is operated with radial type by one source and protection system is composed based on unidirectional power source. But an Insertion of COGN system to power distribution system change existing unidirectional power source system to bidirectional power source. Therefore, investigation to cover whole field of power distribution system must be accomplished such as changing of protection devices rating by increasing fault current, reevaluation of protective coordination. In this paper, simulation using PSCAD/EMTDC was accomplished to analyze effect of COGIN on distribution fault current. Also, the existing protection system of 22.9[kV] power distribution system and customers protection system to protect of COGIN was analyzed and the study on protective coordination between of two protection system accomplished. |