Title Mitigation of Transmission Line Magnetic Field by Installation of Passive Shield-Loop.
Authors 김정부(Kim Jeong-Boo) ; 신구용(Shin Koo-Yong) ; 신명철(Shin Myung Chul)
Page pp.59-61
ISSN 1975-8359
Keywords 전자계 ; 송전선 ; 자계 저감 방법 ; 역상배열 ; 수동루프 ;
Abstract In our country most of transmission lines are double-circuit lines. In these lines, the combining method of increasing conductor height and installation of passive shield-loop to mitigate magnetic field near a transmission line, is a good and feasible method. The basic principle of passive shield loop is that the field from the current induced in the shield loop conductors counteracts the field from the phase conductors. This method applied to domestic transmission lines to meet the magnetic field level, 100, 30, 10 and 4 mG, respectively. In each magnetic field level, the minimum conductor height and passive loop height are presented for the implementation of the practical design.