Title |
Performance Enhancement for Fault Location Using GOOSE Messages |
Authors |
고철진(Go, Chol-Jin) ; 강상희(Kang, Sang-Hee) |
Keywords |
고장거리 추정 ; GOOSE 메시지 ; 리액턴스 효과 IEC 61850 |
Abstract |
IEC 61850 is the worldwide protocol for the substation automation system. IEC 61850 transports the information which consists of different formats such as GOOSE(Generic Object Oriented Substation Event), MMS(Manufacturing Message Specification), SV(Sampled Values) and so on. For real time data transmission, GOOSE can be used. The remote-bus current data which were collected in a local-bus current differential IED can be transmitted to a distance IED at the same location by using GOOSE messages. The distance IED can eliminate the reactance effect by using the transmitted remote-bus current data. This method can improve the performance of the fault location. |