Title |
Analysis of the Harmonic Resonance during Restoration of Primary Restorative Transmission System |
Authors |
이경섭(Lee, Kyeong-Seob) ; 이흥재(Lee, Heung-Jae) |
Keywords |
Harmonic Resonance ; Over-voltage ; Power System Restoration ; PSCAD/EMTDC |
Abstract |
Power system restoration following a wide area or complete blackout starts with energizing primary restorative transmission systems. During this primary restoration process, unexpected over-voltage may happen due to nonlinear interaction between the unloaded transformer and the transmission system. This is known as the harmonic resonance phenomenon that may cause burning out of transformer or other devices. Since the harmonic resonance originates from the nonlinear characteristics, it is very difficult to predict the occurrence of this phenomenon. This paper reports the analyses of the harmonic resonance occurred in domestic power system. Various analyses and results of the harmonic over-voltage is presented based on the PSCAD/EMTDC simulations. |