Title |
Robust Decoupling Digital Control of Three-Phase Inverter for UPS |
Authors |
박지호(Park, Jee-Ho) ; 허태원(Heo, Tae-Won) ; 신동렬(Shin, Dong-Ryul) ; 노태균(Roh, Tae-Kyun) ; 우정인(Woo, Jung-In) |
Keywords |
Deadbeat Control ; Decoupling ; Predictive Control ; State Observer ; Disturbance Observer ; DSP |
Abstract |
This paper deals with a novel full digital control method of the three-phase PWM inverter for UPS. The voltage and current of output filter capacitor as state variables are the feedback control input. In addition, a double deadbeat control consisting of a d-q current minor loop and a d-q voltage major loop, both with precise decoupling, have been developed. The switching pulse width modulation based on SVM is adopted so that the capacitor current should be exactly equal to its reference current. In order to compensate the calculation time delay, the predictive control is achieved by the current¡¤voltage observer. The load prediction is used to compensate the load disturbance by disturbance observer with deadbeat response. The experimental results show that the proposed system offers an output voltage with THD less than 2% at a full nonlinear load. |