Title |
Analysis of Cold Gas Flow in Puffer Type GCB Considering the Real Gas Property of SF_6 |
Keywords |
Puffer GCB ; SF_6 gas ; real gas property ; state equation ; FVFLIC method |
Abstract |
To analyze the performance of the gas circuit breaker(GCB), the flow field variables such as temperature, pressure and density should be evaluated accurately In the puffer chamber of puffer type GCB, the pressure rise may Exceed 20 bar and in this range of high pressure, SF_6 gas deviates the ideal gas property. Therefore, the real gas property of SF_6 should be taken into consideration for the accurate analysis of flow field. This paper presents the analysis technique of cold gas flow in GCB employing the real gas state equation of SF6. The FVFLIC method is Employed to solve the axisymmetric Euler equation. To reduce the computational effort of real gas state equation, the relationship between density and pressure is approximated by the polynomial at the temperature of 300K. The proposed method is applied to the test GCB model and simulation results show good agreement with the experimental ones. |