Title |
Measurement of Radiation Intensity of the High-Pressure and Large-Current Arc |
Authors |
송기동(Song, Ki-Dong) ; 오연호(Oh, Yeon-Ho) ; 정진교(Chong, Jin-Kyo) ; 조용성(Cho, Yong-Sung) |
Keywords |
radiation ; arc ; circuit breaker ; spectroscope ; arc temperature |
Abstract |
This paper presents the measured radiation intensity of high-pressure and large-current arc with the current. In order to measure the radiation intensity of large-current arc, a model circuit breaker was specially designed and manufactured and the method using an astronomical telescope was utilized after various measuring methods were investigated. A trigger system was designed and fabricated to coincide the time of desired current with the exposure time of 1ms of the spectroscope. A high-speed camera was used to investigate the shape and behavior of the arc and the captured results have been used to calculate the radiation energy. The calculated arc temperature with Boltzmann plot method using the measured radiation intensity have 18,000~27,000K to the current 4kA~15kA. And also, using the calculated arc temperature and the captured arc shape the radiation energy of the current 5kA~15kA were calculated with 8×10^5~4.0×10^6W/m respectively. |