Title |
The Effects of Design Parameter to Interrupt Optimally for High Voltage CL Fuse |
Authors |
이세현(Lee, Se-Hyeon) ; 한상옥(Han, Sang-Ok) |
Keywords |
Current-Limiting Fuse ; Interrupting Characteristic ; Arcing ; Optimal Design |
Abstract |
The fuse used in the high voltage distribution line often fails due to the active ionization caused by the strong electric field at fuse terminal. To suppress the ionization at the high voltage and high capacity current limiting fuse, the particle size and compactness of silica sand, the design, length, notch number and material of element, the diameter and length of fuse body must be considered carefully. However, these are not many proper which is treated with the inherent interrupting characteristics from many parameters at present. Because of these reasons, time and effort are needed to develop the new type fuse by the fuse designers in relation with the inherent characteristics from each of parameters. In this paper we choose 7 parameters with weight value based on study and experimentation and analyzed the characteristics of arcing period. In addition, we proposed the experimental method to experimentation and analyzed the characteristics of arcing period. In addition, we proposed the experimental method to extract the optimal design parameters with minimal effort as related the mutual effect from each of the parameters. |