Title |
A Novel Sensitivity Verification Method for the UHF Partial Discharge Detection System in Gas Insulated Switchgear (GIS) |
Authors |
구선근(Gu, Seon-Geun) ; 박기준(Park, Gi-Jun) ; 윤진열(Yun, Jin-Yeol) |
Keywords |
UHF ; Partial discharge ; GAS ; network analyzer |
Abstract |
We proposed a new sensitivity verification method for the UHF partial discharge(PD) detection system. Initially, we measure the UHF power induced by 5 pC PD which takes place near UHF sensor. Subsequently, we inject the swept UHF signal from a network analyzer into the GIS and measure the attenuation of the signal along the 71S Both the UHF power by 5 pC PD and the attenuation make it possible to verify the sensitivity and spatial coverage of the PD detection system. This method doesn `t require the calibration of injected pulse type UHF signal into the GIS and makes us precisely measure the attenuation in frequency domain. |