Title |
A Study on the Partial Discharge Phase Properties with Branch Type Eleotrical Tree Growth in XLPE Cable Insulation |
Authors |
강동식(Gang, Dong-Sik) ; 선종호(Seon, Jong-Ho) ; 김위영(Kim, Wi-Yeong) ; 이홍식(Lee, Hong-Sik) ; 박정후(Park, Jeong-Hu) |
Keywords |
Electrical tree ; XLPE ; Partial discharge ; Aging ; φ -q-n ; normalized aging rate |
Abstract |
In order to improve the reliability of XLPE cables, it is necessary to find the useful diagnostic parameter according to long term aging. This paper described the change of partial discharge(PD) phase Properties of XLPE cable insulation with branch type electrical tree degradation. for long term aging. To understand the PD Properties with φ -q-n distributed shape of XLPE insulation, specimens were prepared by 22.9㎸ distribution cable and made in a type of block(16×16×3[mm]). Ogura needles having tip radius of l0μ{ textrm} m were inserted into each block pieces. The measuring system was consisted of PD detector, digitizer for digital conversion, VXI system for signal processing. The PD properties of the specimens were measured from initiation of tree to breakdown and their characteristics were analyzed. We analyzed the relationship between electrical properties(PD Quantity, PD initiation angle, PD extinction angle, PD occurrence angle : (PD extinction angle - PD initiation angle)) and the normalized aging rate. We found PD parameter, PD initiation angle and occurrence angle, which are a useful diagnostic parameter in estimating the branch type electrical tree for XLPE insulation condition. |