A Study on the Algorithm for Detection of Partial Discharge in G15 Using Wavelet Transform |
Keywords |
Partial Discharge ; Wavelet Transform ; Gas Insulated Switchgear ; Mother Wavelet |
Abstract |
Gas insulated switchgear(GIS) is an important equipment in a substation. It is highly desirable to measure a partial discharge(PD) in GIS which is a symptom before insulation breakdown occurs. The issue is that the PD signal is weak and sensitive to external noise. In this paper, the algorithm for detection of PD in GIS using wavelet transform is proposed. The wavelet transform provides a direct quantitative measure of spectral content, "dynamic spectrum", in the time-frequency domain. The recommended mother wavelet is 'Daubechies' wavelet. 'db4', the most commonly applied mother wavelet in the power quality analysis, can be used most properly in disturbance phenomena which occurs rapidly for a short time. Through the procedure of wavelet transform, noise extraction and reconstruction, the signal is Analyzed to determine the magnitude of PD in GIS. In experimental results, we can know that partial discharge is exactly detected in combination of Dl and D2 using wavelet transform.transform. |