Title |
UHF Narrow Band Type Partial Discharge Diagnosis Method for the Internal Insulation Performance Verification of the Gas Insulated Switchgear |
Authors |
송원표(Song Won-Pyo) ; 김정배(Kim Jung-Bae) ; 김민수(Kim Min-So) ; 정재룡(Jung Jae-Ryong) ; 박승재(Park Seung-Jae) ; 고희석(Ko Heui-Suk) |
Keywords |
GIS ; UHF method ; Partial Discharge Diagnostic ; Frequency Analysis ; Phase Analysis |
Abstract |
A method for partial discharge diagnosis based on UHF narrow band type for GIS has been developed and calibrated. In generally, PD cannot be directly measured under on-line condition, but we can indirectly measure the electromagnetic wave made by PD using the high-frequency antenna. Compared with VHF band, electromagnetic waves of UHF band have a low influence for external noise in high-voltage substation. Therefore, we can detect the real abnormality with several pC in GIS using UHF narrow-band type method. For the case of no internal VHF sensor for GIS of the domestic substation, it has applied to use the external UHF sensor attached in spacer in GIS of existing substation. In this paper, we firstly described the technique of partial discharge measurement using frequency analysis and phase analysis in UHF band. Secondly, we presented the results of sensitivity test, the relationship of dBm-pC and diagnosis result of the cause of PD source by phase analysis. And then, we report the diagnosis result of partial discharge on the real GIS in domestic substation. These results make above method applicable for measurement of quantity and cause of PD for real operation GIS in high-voltage substation. |