Title |
Development of The Accurate Potential Transformer with Wide Ratio Error and Its Application |
Authors |
권성원(Kwon, Sung-Won) ; 정재갑(Jung, Jae-Kap) ; 이상화(Lee, Sang-Hwa) ; 김명수(Kim, Myung-Soo) |
Keywords |
Potential Transformer(PT) ; Wide Ratio Error PT ; PT Comparator ; Linearity ; Correction |
Abstract |
A accurate potential transformer(PT) with the nominal ratio errors in the wide range of - 9 % to + 11 % has been developed. The developed wide ratio error PT can be used to evaluate the linearity of the PT comparator by comparing both the theoretical values as standard values and experimental values of the PT. The new method has been successfully applied for calibration and correction in the PT comparator including very low ratio error values from pm0.005% to pm0.3% belonging to industry. |