Title |
An Adaptive Reclosing Technique Considering the Distributed Generation |
Authors |
서훈철(Seo, Hun-Chul) ; 김철환(Kim, Chul-Hwan) ; 여상민(Yeo, Sang-Min) |
Keywords |
autoreclosing ; distributed generation ; transient stability ; EMTP MODELS |
Abstract |
The autoreclosing is applied to power system for maintaining system stability and continuity of supply. Developments on distributed generation(DG) grows significantly by environmental issues and economical issues. If the DG is connected to distribution system, the DG influences the technical aspects such as power quality, protection and stability. It causes the challenges to protection, especially to reclosing. In order to achieve reliability and safety of the distribution system, the rules and guidelines suggest that the DG units should be rapidly disconnected from the network before the reclosing. If the DG is disconnected whenever the fault occurs, it cannot be utilized effectively. This paper presents the adaptive reclosing algorithm considering the DG. The algorithm consists of angle oscillation's judgment, EEEAC(Emergency Expanded Equal-Area Criterion), calculation of optimal reclosing time and re-connection algorithm. The simulation is implemented for the DG technology by using EMTP MODELS. The simulation results show that the transient stability is maintained and the DG is protected against disturbance. |