Title |
On-Site Evaluation Technique of Current Transformer Comparator System |
Authors |
정재갑(Jung, Jae-Kap) ; 이상화(Lee, Sang-Hwa) ; 권성원(Kwon, Sung-Won) ; 강전홍(Kang, Jeon-Hong) ; 김명수(Kim, Myung-Soo) |
Keywords |
Current transformer ; Current comparator ; Traveling standard ; Ratio error ; Phase angle error ; Burdens ; Linearity |
Abstract |
A recently developed methods for on-site calibration of the current transformer (CT) comparator system have been reviewed in the paper. The method utilizes several traveling standards, which consist of the CT, non-reactive standard resistors, wide ratio error CT, and shunt resistors. The traveling CT is used for absolute evaluation of a standard CT belonging to industry. The non-reactive standard resistors and a wide ratio error CT are used for the linearity check of errors in the current comparator. The shunt resistors are used for evaluation of CT burden of industry. |