Title |
A Dynamic Characteristics on Non-linear Voltage Electric Equipment under Voltage Sag |
Authors |
이현철(Lee, Hyun-Chul) ; 정성원(Jeong, Sung-Won) ; 김재현(Gim, Jae-Hyeon) ; 이근준(Lee, Geun-Joon) |
Keywords |
Power Quality ; Voltage Sag ; CEBMA curve |
Abstract |
In this study, a transition of power quality was characterized by non-linear voltage electric equipments under voltage sag. The test was inputted voltage sag to IPC(Sag Generator) from AVR, and then to equipments by IPC which adjust voltage magnitude and duration. The load test which non-linear voltage electric equipments used PLC, Magnetic Contactor, SMPS, HID Lamp. The test result was different from each other according to a manufacturing companys, models, and equipments. PLC was greatly described to be stabilized voltage sag in case of no load then rated load. Magnetic Contactor was made a difference to phase angles on voltage sag, which was 0°, 30°, 60°, 90°. HPD Lamp was described to be stabilized the sodium lamp, and to be unstabilized the metal hailed lamp. The test result was showed CBEMA curve that stand for evaluated responsiveness of voltage sag. This study was tested description to dynamic characteristics on non-linear voltage electric equipment under voltage sag. There was hoped that power system designed the essential particulars. |