Title A Case Study on Malfunction of OCGR and Inaccuracy of Watt-hour Meter in Distributed Generation System
Authors 신동열(Shin, Dong-Yeol) ; 박용우(Park, Yong-Woo) ; 차한주(Cha, Han-Ju)
Page pp.1349-1355
ISSN 1975-8359
Keywords Distributed generation system ; OCGR trip ; Metering errors ; Fault event
Abstract The paper shows the analysis of operating conflict of OCGR trip events and metering errors in the photovoltaic generation, wind generation distributed generation customers with no defect of the distributed generation facilities, which are connected to 22.9kV distribution lines. To analyze problems with metering errors and OCGR fault event, a power quality analyzer and PSIM program were used to test the field and to simulate in Sun-Cheon photovoltaic generation and Seo-Cheon photovoltaic generation customers. With the trial distribution line, the result of analysis was verified to prove with the same situation of the actual field. This paper suggests short term and long term countermeasures of OCGR fault events, analysis of over and shortage of metering errors in distributed generation customers.