Title |
An Analysis of Power System Stability(PSS) Effect with 135MVA Hydro Generator |
Authors |
옥연호(Ok, Yeon-Ho) ; 이은웅(Lee, Eun-Woong) ; 변일환(Byun, Ill-Hwan) ; 오석영(Oh, Sueg-Young) |
Keywords |
PSS ; Excitation System ; Test ; Protection ; Frequency |
Abstract |
As national power consumption every year increases, the power plant which is in the process of planning tries to establish high-capacity generator. The power system tends to become a large size. With the progress of electronic components, the control systems of the generator have been digitalized and rapid-response control system is possible. However, the minute frequency vibration of grid occurred with the effect of rapid-response control system. To solve these problem, PPS(Power System Stability) has been introduced since 2004, and it has being installed and applied to the thermal and nuclear power plant which are high-capacity, over 800MVA. However the minute frequency vibration is gradually changed to the bigger frequency vibration by fast-action control system, and this regional frequency fluctuation might be diffused wide area. Therefore, it is applied to the hydro generator which is small with fast-action governor system, and it is necessary to control the minute frequency vibration to prevent to diffuse. In this paper, the effect will be proved by establishing PSS on the Hydro-Generator which has both digital excitation and governor system for the first time in Korea. |