Title |
An Analysis of UV Detected Images and Safety Standards in Discharging Model |
Authors |
송길목(Shong, Kil-Mok) ; 김영석(Kim, Young-Seok) ; 정진수(Jung, Jin-Soo) |
Keywords |
Ultraviolet rays image ; Ultraviolet rays camera ; Ultraviolet rays judgment method ; Risk factor |
Abstract |
This paper was studied about the aging judgment method by ultraviolet rays image to happen in electric power equipment using ultraviolet rays camera. We established the aging judgment method as follows; 20% within of risk factor of insulation state of electrical facility that ultraviolet rays image does not show is "good or recognition". 30^~50% within of risk factor is "check", 50^~60% within of risk factor is "inspection" and 60% above of risk factor is "replacement". This method will be utilized for the inspection about electrical facilities. |