Title |
The Research for a Structure of Current Limiter using a Phasic Similitude of Magnetic Circuit |
Authors |
지근양(Ji, Geun-Yang) ; 민경일(Min, Kyung-Il) ; 이수원(Lee, Su-Won) ; 장봉환(Jang, Bong-Hwan) ; 문영현(Moon, Young-Hyun) |
Keywords |
Current Limiter ; Fault Current ; Magnetic Switching ; Circuit Breaker ; Magnetic Flux ; Phasic Similitude ; Magnetic Circuit |
Abstract |
In this paper, current limiter using a magnetic switching which is based on magnetic flux change in the case of fault is proposed. This current limiter consists of iron-core and three parts of coils. One is the primary coil connected to the power system. Another is the secondary coil wound to the opposite direction of the primary coil's winding. The other is the secondary of the secondary coil which is a movable copper plate winding and located below the secondary coil. In the normal state, the magnetic flux produced in the primary and secondary coils flows to the opposite directions each other and becomes to be canceled out. Therefore the voltages induced between the coils are zero. In the case of a fault, at the moment of a fault occurrence recognition, the switch connected to a secondary coil is opened and the secondary of the secondary coil is pulled out to the outside of the iron-core. Then, magnetic flux becomes to flow through the iron-core. Accordingly, the voltage is induced between the both ends of the primary coil and makes the current reduced. Therefore it is possible to cut off the circuit breaker easily with the proposed current limiter. This paper analyzes the current limiting effects and the detailed results are given. |