Title |
Suitability Evaluation on Joint Operation of Neutral Wire and Overhead Grounding Wire through Lightning Surge Analysis in Combined Distribution System |
Authors |
정석산(Jeong, Seok-San) ; 이종범(Lee, Jong-Beom) ; 김용갑(Kim, Yong-Kap) ; 송일근(Song, Il-Keun) ; 김병숙(Kim, Byoung-Suk) |
Keywords |
Combined distribution system ; Overhead line ; Underground cable ; Neutral wire ; Overhead ground wire ; Joint operation ; EMTP |
Abstract |
This paper studies the validity about a joint operation of neutral wire and overhead grounding wire in combined distribution systems. The overhead grounding wire and neutral wire are currently installed separately and grounded by common. However there is no any ineffectiveness or electrical problem in case of the proposed system, such system can be operated at real distribution system. Therefore this paper describes the suitability of a joint operation through lightning surge analysis on combined distribution systems. Lightning surge analysis is carried out by EMTP/ATPDraw to obtain the overvoltage of overhead line and underground cable in various conditions such as locations and current types of lightning stroke. Overvoltage gained by the analysis show that the insulation strength of the joint operation case is not stable compare with the current operation case. |