Title |
A Development of Reduced-scale Model to Predict of Environmental Characteristics of AC/DC Hybrid Overhead Transmission Line |
Authors |
최인혁(Choi, In-Hyuk) ; 신구용(Shin, Koo-Yong) ; 이동일(Lee, Dong-Il) ; 임재섭(Lim, Jae-Seop) ; 김영홍(Kim, Young-Hong) ; 맹종호(Maeng, Jong-Ho) ; 주문노(Ju, Mun-No) |
DOI |
https://doi.org/10.5370/KIEE.2012.61.5.676 |
Keywords |
AC/DC hybrid ; HVDC ; Reduced-scale model ; Environmental characteristics |
Abstract |
To review application of HVDC (High Voltage Direct Current) transmission line to HVAC T/L in operation, reduced-scale model was designed and manufactured. The arms of model were designed to change height and interval of conductors. Electrical environmental interferences were estimated by various configuration of AC 345kV and DC 250kV T/L. The interferences such as electric field intensity and ion current density were measured and converted reduced-scale factor to full-scaled. Additionally, effects between AC and DC T/L were studied. |