Title |
The Development of an Operating System for Load-following Real-time Transformer Loss Minimization and Economic Analyses on its' Test Operation |
Authors |
이옥배(Lee, Ok-Bae) ; 안재경(Ahn, Jae-Kyoung) |
DOI |
https://doi.org/10.5370/KIEE.2012.61.6.797 |
Keywords |
Power transformer ; Loss minimizing ; SCADA ; Economic analysis |
Abstract |
In this paper, for minimizing the real-time operating load losses of the power transformer, a SCADA optimum operating system was developed, and the economic analyses on the test operation were performed. Transformer loss DB which reflects the economic integration operation criteria was constructed by referring the transformer manufacturer's loss data(iron loss, copper loss). Based on the loss DB, each substation transformer real-time loss was calculated according to the size of the transformer loads, and if integration or separation transformer operating conditions minimizing the loss are met, then a window pops-up and the dispatcher performs the substation equipments operation according to the procedure provided by this system. With the existing SCADA main program, the relation database of the substation facilities and integration/separation operation algorithm were developed and applied to Auto MTR Processor and pconn Processor Task module. Seven stations test data for seven months were analyzed for the economic analyses, and the results showed that Cost-Benefit ratio was 2.64, and IRR(Internal Rate of Return), 36%, which asserted the economic justification of the proposed system. |