• 대한전기학회
Mobile QR Code QR CODE : The Transactions of the Korean Institute of Electrical Engineers
  • COPE
  • kcse
  • 한국과학기술단체총연합회
  • 한국학술지인용색인
  • Scopus
  • crossref
  • orcid
Title A Study on Protective Coordination Setting of Positive Offset Mho Loss of Field Relay
Authors 김광현(Kim, Kwnag-Hyun) ; 박지경(Park, Ji-Kyung) ; 김준혁(Kim, Jun-Hyeok) ; 김두웅(Kim, Doo-Ung) ; 강성범(Kang, Sung-Bum) ; 김철환(Kim, Chul-Hwan) ; 유영식(Lyu, Young-Sik) ; 양정재(Yang, Jeong-Jae) ; 고윤태(Ko, Yun-Tae)
DOI https://doi.org/10.5370/KIEE.2016.65.8.1326
Page pp.1326-1333
ISSN 1975-8359
Keywords Loss of Field ; Coordination ; UEL ; 40Ry ; GCC ; SSSL
Abstract It is important to clear the fault and prevent resulting in damage to power system. Although the frequency of generator internal fault is relatively low, it can lead to incalculable damage to power system as well as generator. Especially, loss of field on generator can cause the generator to lose synchronism for a short time if it is not removed promptly. Therefore, it is needed to conduct research on loss of field relay for detecting or clearing the loss of field. However, the setting of the relay may vary in generator operator or engineer, and the relay is not coordinated well with other elements associated with loss of field. In this paper, we address specifically the coordination of positive offset mho loss of field relay which is one of the protection schemes for loss of field. Computer simulations are performed by using ElectroMagnetic Transients Program-Restructured Version (EMTP-RV) based on actual data.