Title |
Historical Operation Characteristic Analysis of Energy Storage System for Governor Free using Simulink Model |
Authors |
조성민(Cho, Sung-Min) ; 임지훈(Im, Ji-Hoon) ; 이성은(Lee, Sung-Eun) |
DOI |
https://doi.org/10.5370/KIEE.2017.66.6.905 |
Keywords |
Battery energy storage system ; Frequency control ; Governor free ; Spped regulation rate |
Abstract |
As the development of BESS(Battery Energy Storage System), the application of BESS in load frequency control is considered as effective method. So, KEPCO(Korea Electric Power Corporation) have installed about 236MW ESS for GF(Govner Free) function from 2014. In this paper, we implemented Simulink Model for KEPCO GF ESS and analyzed one year historical operation data generated by Simulink model and actually measured frequency data. The operation results were divided into action for maintaining SOC and frequency. In addition, we also analyzed cycle life of GF ESS using two ESS cycle life model. We concluded the ESS cycle life models are not appropriate, because Most of the SOC swing in operation results are below 10%. |