Key words
               
               Direct Current(DC), Direct Current Circuit Breaker(DCCB), Superconductor, Arc, Coil
             
            
          
         
            
                  1. Introduction
               Recently, there has been a huge increase in power demand in the world. Not only the
                  steady usage of power apparatus, but also new devices such as smart-phone, electric
                  vehicle have developed as new demands. It is urgent that measures to supply the electric
                  power for the growth are established. There is a method using direct current electricity
                  as a measure of energy measures. Unlike existing AC, DC has a lot of advantages like
                  high stability and low power dissipation. By using this, many researches have been
                  performed as HVDC or MVDC, high voltage transmission, or the dc system for power supply.
                  Also due to environmental issues, renewable energy, such as wind and solar power,
                  is growing rapidly. These kinds of power sources generated in DC is connected to the
                  large system as distributed generation system(1).
               
               Using DC as transmission and distribution has many benefits, but there is a problem
                  to commercialize. The AC current has 2 zero current points in one cycle. This makes
                  the interruption easily. However the DC current has no zero current point, and a high
                  arc voltage appears across the DC circuit breaker when it conducts breaking operation.
                  If a high arc voltage damages the insulation or exceeds the capacity of the breaker’s
                  circuit cut off, it can lead to blackout, or in the worst, to the collapse of the
                  entire grid. It is critical to make DC grid because of the variety of DC power sources
                  and DC demanding electric apparatus. To make the grid, DC circuit breaker is the most
                  core technology. Only if the development of the DC circuit breaker should proceed,
                  DC current and the grid will use efficiently and stably(2). 
               
               In this study, the coil–typed superconductor DC circuit breaker was proposed to improve
                  the interruption performance of DC current. In prior to construct in real, an in-depth
                  determination of DCCB applying to a superconductor is essential. Accordingly, operation
                  and protection range of DCCB was analyzed depending on each input voltage. EMTDC/
                  PSCAD had used to design the simulation.
               
             
            
                  2. Coil type Superconductor DC circuit
               DC circuit breaker simply consisted of two parts; coil type superconductor for the
                  current limitation and mechanical DC circuit breaker for interrupting the fault current.
                  Fig. 1 represents the configuration of coil type superconductor DC circuit breaker. In normal
                  operation, current flows without any disturbance. When the fault occur, the superconductor
                  limits the initial fault current. After the operation, mechanical DC circuit breaker
                  cut off the current with L-C oscillation.
               
                
                  
                  
                        
                        
Fig. 1. Configuration of coil type superconductor DC circuit breaker
 
                      
                  
               
                
               
                     2.1 Superconducting coils
                  In normal superconducting state, there is no impedance in superconductor. By this
                     reason, power could supply without any electric losses or power burden. Upon the occurrence
                     of a fault, however, when the amplitude of fault current exceeds the critical current
                     of the superconductor, it generates a specific high impedance in a few milliseconds
                     according to their unique characteristic. This behavior is named as quenching. Equation (1) represents the quenching characteristics of the superconductor. The value Rm is the
                     maximum resistance of the superconductor in the quenching state. Tsc is the time constant
                     of the superconductor during transition from the superconducting state to the normal
                     state. To is the time to start the quenching(3).
                  
                  In coil type superconductor, the constant for Rm= 8Ω and Tsc=0.75 msec. The reason
                     is the peak resistance value of the superconductor was modeling to be within 2 msec.
                     Fig. 2 represents the coil type superconductor quenching characteristic graph of coil type
                     superconductor(4).
                  
                   
                     
                     
                           
                           
Fig. 2. Coil type superconductor quenching characteristic graph
 
                         
                     
                  
                   
                     
                     
 
                     
                     
                     
                  
                   
                
               
                     2.2 Configuration of circuit
                  The mechanical DC circuit breaker is comprised of 3 circuits; breaking circuit, commutation
                     circuit and absorber circuit.
                  
                  First, there are mechanical contact and arc box in the breaking circuit. Arc box is
                     placed for arc characteristics in the circuit breaker. As previously stated, DC interruption
                     is usually accompanied with arc. To implement the arc characteristics in the simulation,
                     arc modeling is indispensable. Mayr arc model had used to apply arc box modeling.
                     Coil type superconductor DCCB is aimed to adapt to the DC links between the distributed
                     power systems. This part is suited for high voltage. Mayr arc model has selected to
                     arc model because it is appropriate in high voltage and low current. 
                  
                  Also Mayr assumed that the arc has fixed across- sectional area losing energy only
                     by radial thermal conduction. The Mayr model is suited for modeling of the arc in
                     the vicinity of current zero when the temperature of the plasm is below 8000 K(5). Arc box was modeled based on Equation (2).
                  
                   
                     
                     
 
                     
                     
                     
                  
                  Second, inductance (L) and capacitance(C) are the elements of the commutation circuit.
                     The momentary mechanical contact is opened, the current flows into commutation circuit
                     and induces oscillation. By the function of the oscillation current, zero current
                     could be induced. Equation (3) is the arc current occurred in between the mechanical contact in the breaking circuit.
                  
                   
                     
                     
 
                     
                     
                  
                  The arc time constant is 0.3 uF and arc cooling power is 50 MW. The constants for
                     the commutation circuit were set at L = 300 uH and C = 30 uF(6). 
                  
                  At this point, $w _ { c } = \sqrt { 1 / L C }$.
                  Lastly, an arrester was placed in the absorber circuit. The residual current was discharged
                     through the arrester. 120 kV of arrester voltage rating was inserted into the simulation(7,8).
                  
                   
                
             
            
                  3. Simulation Analysis
               
                     3.1 Simulation modeling
                  In this paper, we would like to confirm the protection range of DCCB according to
                     coil type superconductor. Mechanical DCCB were designed by rating voltage of 120 kV.
                     The DC sources that were applied to the simulation were 120 kV, 180 kV and 240 kV
                     in 60 kV interval each. The fault occurred at 1 second after beginning of the simulation,
                     and the fault duration was 0.5 sec. As the circuit breaker had mechanical contacts
                     to operates, accordingly the opening operation would have of 10ms delay time. It works
                     at 1.010 sec. The figures showed that the line resistance was set at 2.5 Ωand load
                     resistance was set at 24.77Ω
                  
                   
                
               
                     3.2 Simulation results
                  Fig. 3 shows the current characteristics when the applied voltage is 120 kV DC. It shows
                     behaviors of CB with and without coil type superconductor. When the power was applied
                     to the without superconductor, a 4.39kA steady- state current flowed into the circuit.
                     Through the simulated fault at 1 sec, fault current of 12.6 kA was generated. After
                     10 msec, mechanical contact in the breaking circuit was operated and oscillation current
                     flowed with commutation circuit. At this moment, oscillation current increased maximum
                     21.2 kA. It took 13.08 sec for breaking operation. In the end, the residual current
                     discharged through the arrester in 4~5ms. On the other hand, when the DCCB had applied
                     superconductor, fault current was limited to 7.3 kA by quenching operation of superconductivity.
                     After 10ms mechanical circuit breaker worked and whole interruption operation ended
                     in 10.08 msec.
                  
                   
                     
                     
                           
                           
Fig. 3. DC current characteristics between with and without superconductor when the
                              input voltage is 120 kV
                           
 
                         
                     
                  
                  Fig. 4 represents the current characteristics in 180kV. At first 6.59 kA of steady state
                     current flowed in normal condition. When the fault occurs, 19.2kA of fault current
                     was generated in the DC circuit breaker which is composed without superconductor.
                     After the operation of the contact, oscillation fault current increased until 35.1kA.
                     And the whole interruption was done in 23.40 msec. When the DC circuit breaker applied
                     a superconductor, the fault current that limited by superconductivity was generated
                     about 10.8 kA. As aforementioned mechanism, it took only 12.18 msec to cutoff the
                     fault current.  
                  
                   
                     
                     
                           
                           
Fig. 4. DC current characteristics between with and without superconductor when the
                              input voltage is 180 kV
                           
 
                         
                     
                  
                  Fig. 5 shows characteristics in input voltage of 240 kV. The figure of 8.79 kA steady state
                     current flowed in normal state. In the without superconductor, 25.22kA of fault current
                     was generated. After it took same mechanism as above-mentioned. In breaking circuit,
                     there is no current flow after oscillation, however, 10.3 kA of current flows through
                     absorber circuit. Indeed interruption had failed. 
                  
                   
                     
                     
                           
                           
Fig. 5. DC current characteristics between with and without superconductor when the
                              input voltage is 240 kV
                           
 
                         
                     
                  
                  Whereas in the case with superconductor, 13.7kA of limited fault current was generated.
                     The whole interruption operation has done in 14.9 msec.  
                  
                  Results show that when the input voltage was 120 kV, fault current was interrupted
                     stably without superconductor. However, when the input voltage was 180kV, the both
                     fault current and interruption time was increased than before. At last interruption
                     has failed in 240 kV. On the other hand, when the superconductor has applied to DC
                     circuit breaker, the whole three cases were cut-off stably within 16 msec.
                  
                   
                
               
                     3.3 Consideration
                  Fig. 6 shows the interruption time and power burden graph according to rise of input voltage.
                     The power burden represents energy that generates in the circuit breaker which is
                     calculated by integration of the rated voltage and rated current. This is the case
                     of 120 kV rated DC circuit breaker with the coil type superconductor. It could find
                     that although the input voltage had increased, cut-off operation worked in a very
                     high speed. Also it only took 14.9 msec when the input voltage was 240 kV. Therefore
                     protection range could enlarge at least 2 times when superconductor applied. According
                     to AC circuit breaking standard, fault current should cut-off in 3~5 cycles. But the
                     figure represents the interruption time in the full grid with all electric devices.
                     When we check the operation speed of current limiter only, it should have to operate
                     within 8 msec. However, this is the case of DC circuit breaker with coil type superconductor.
                     Therefore the maximum interruption time was computed at 16 msec in this paper. As
                     follows the standard, the figure in the data represents that interruption time is
                     appropriate.  
                  
                   
                     
                     
                           
                           
Fig. 6. Interruption time and power burden of coil type superconductor applied DC
                              circuit breaker according to increase of input voltage
                           
 
                         
                     
                  
                  When the massive power burden had occurred, the heat generated within the circuit
                     increases and resulted electric breakdown and deterioration as breaker failure. Thus,
                     a stable cut-off criterion was calculated as a point where it would take twice as
                     much power as the initial power burden. At least 4.35 MVA was imposed on the approval
                     of 120 kV. At 240 kV, approximately twice the 8.3 MVA power burden was generated.
                     Therefore, if superconductor applied to 120 kV rated DC circuit breaker, the maximum
                     protection range was calculated at 240 kV that twice as much as the rated.
                  
                  At last, depending on the maximum resistance and capacity of coil type superconductor,
                     the protection range can be increased.
                  
                   
                
             
            
                  4. Conclusion
               In this study, coil-type superconductor DC circuit breaker was proposed which is combined
                  with coil-type superconductor and mechanical DCCB. Protection range had checked with
                  or without superconductor in the same DCCB capacity.
               
               The result is telling that in the without superconductor DCCB system, the tolerable
                  cutoff voltage of DCCB was within 20 to 30 % of the rated cutoff voltage. However,
                  when the superconductor applied, the range of the protection has enlarged within 150
                  to 200 %.
               
               If the coil type superconductor DCCB is commercially available in the future, the
                  possibility of blocking failure will be significantly lowered and the DC grid reliability
                  will be enhanced. Further tests are to be demonstrated by actual experiment of coil-type
                  superconductor DCCB.
               
             
          
         
            
                  감사의 글 
               Following are results of a study on the “Leaders in Industry-university Cooperation
                  +” Project, supported by the Ministry of Education and National Research Foundation
                  of Korea.
               
             
            
                  
                     References
                  
                     
                        
                        Blaabjerg Frede, Chen Zhe, Kjaer Soeren Baekhoeh, Sep 2004, Power electronics as efficient
                           interface n dispersed power generation system, IEEE Transactions on Industrial Electronics,
                           Vol. 19, No. 5

 
                     
                        
                        Leon Garcia W. R., Bertinato A., Tixador P., Raison B., Luscan B., 년도, Full-selective
                           protection strategy for MTDC grids based on R-type superconducting FCLs and mechanical
                           DC circuit breaker, Renewable Power Generation(RPG) 2016, 5th IeT international Conference
                           on, 10.1049/cp.2016.0564

 
                     
                        
                        Sung Byung Chul, Park Dong Keun, Park Jung-Wook, Ko Tae Kuk, Jul 2009, Study on a
                           series resistive super- conductor to improve power system transient stability : Modeling,
                           Simulation and experimental verification, IEEE Transactions on Industrial Electronics,
                           Vol. 56, No. 7

 
                     
                        
                        Ou Ran, Xiao Xian-Yong, Zou Zhi-Ce, Zhang Yi, Wang Yu-Hong, Oct 2016, Cooperative
                           control of superconductor and reactive power for improving the transient voltage stability
                           of grid-connected wind farm with DFIGs, IEEE Transactions on Applied Superconductivity,
                           Vol. 6, No. 7

 
                     
                        
                        Mahajan N. S., Patil K. R., Shembekar S. M., FEB 2013, Electric Arc model for High
                           Voltage Circuit Breakers Based on MATLAB/SIMULINK, Interantional Journal of Science,
                           Spritualtiy, Business and Technology (IJSSBT), Vol. 1, No. 2

 
                     
                        
                        Mokhberdoran Ataollah, Carvalho Adriano, Leite Helder, Silva Nuno, 2014, A review
                           on HVDC circuit breakers, Renewable Power Generation Conference (RPG 2014), 10.1049/cp

 
                     
                        
                        Lee Jong-Geon, Khan Umer Amir, Lee Ho-Yun, Lee Bang-Wook, JUN 2016, Impact of SFCL
                           on the four types of HVDC circuit breakers by simulations, IEEE Transactions on Applied
                           Superconductivity, Vol. 26, No. 4

 
                   
                
             
            저자소개
             
             
               
               
            
            1987년 12월 11일 생
            2012년 조선대 전기공학과 졸업(학사)
            2014년 동 대학원 졸업(공학석사)
            2018년 동 대학원 졸업(공학박사)
            Tel : 062-230-7054
            E-mail : no21park@hanmail.net 
            
             
             
               
               
            
            1989년 10월 04일 생
            2012년 조선대 전기공학과 졸업(학사)
            2014년 동 대학원 졸업(공학석사)
            2014~현재 동 대학원 박사 수료
            Tel : 062-230-7054
            E-mail : vjvldnjs@naver.com 
            
             
             
               
               
            
            1965년 12월 22일 생
            2014~현재 조선대학교 대학원 박사 수료
            현재 한국철도시설공단 재직
            Tel : 062-230-7054
            E-mail : yji2012@kr.or.kr 
            
             
             
               
               
            
            1966년 2월 21일 생
            1989년 전북대 전기공학과 졸업(학사)
            1994년 동 대학원 전기공학과 졸업(공학석사)
            2000년 동 대학원 전기공학과 졸업(공학박사)
            현재 조선대 전기공학과 교수, 시민 르네상스 평생교육원 원장, 미래사회융합대학 학장
            Tel : 062-230-7025
            E-mail : hyosang@chosun.ac.kr